Made in USA
UL Listed

EMI RFI power line Filters

EMI RFI power line Filters

This series of Power Line Penetration Filters can be mounted through the outer wall of a shielded enclosure. The filters are RFI secure and supplied with threaded nipple. Filters supplied with bleeder resistor to prevent shock hazard. Filters are also available with surge arresters.

These Filters are available in four series

DMC-FCP-11: (60Hz)

DMC-FCP-12: (400Hz) 100dB attenuation from 100 kHz to 10 GHz measured per MIL-STD-220A full load

DMC-FCP-22: (60Hz)

DMC-FCQ-22: (60Hz) attenuation from 9 kHz to 10 GHz measured per MIL-STD-220A full load.

DMC-FCP-23: (400Hz) 100dB attenuation from 14 kHz to 10 GHz measured per MIL-STD-220A full load.

DMC-FCP-11 Series 60 Hz & DMC-FCP-12 Series available for 400 Hz

Current Line to Ground Voltage Frequency Dimensions (Inches) APPR WT
DMC- Part No (AMPS) VAC VDC (Hz) A B C AWG (LBS)
DMC-FCP·11·5 5 277 600 0-60 9 4 4 10 10
DMC-FCP·11·2×5 * 2×5 277 600 0-60 9 8 4 10 15
DMC-FCP·11·2×5 ** 2×5 277 600 0-60 9 8 4 10 15
DMC-FCP·11·30 30 277 600 0-60 20 4 4 10 20
DMC-FCP·11·2×30 * 2×30 277 600 0-60 20 7 4 10 30
DMC-FCP·11·4×30 ** 4×30 277 600 0-60 20 14 4 10 30
DMC-FCP·11·60 60 277 600 0-60 24 4 4 6 25
DMC-FCP·11·60 60 277 600 0-60 24 4 4 6 25
DMC-FCP·11·100· 100 277 600 0-60 29 4 ½ 4 ½ 2 30
DMC-FCP·11·200 200 277 600 0-60 31 8 5 ½ 4/0 60
DMC-FCP·11·225 225 277 600 0-60 31 8 5 ½ 4/0 60
DMC-FCS-4×200*** 200 277 600 0-60 34 24 5 ½ 4/0 60

*Dual filters may be used in 3 phase systems up to 480 volts phase to phase

**Special Filter 100dB from 14kHz to 13GHz

***Special Filter 100dB from 30MHz to 13GHz

DMC-FCP-22 Series 60Hz & DMC-FCP-23 Series available for 400Hz

Current Line to Ground Voltage Frequency Dimensions (Inches) APPR WT
DMC- Part No (AMPS) VAC VDC (Hz) A B C AWG (LBS)
DMC-FCP-22-25 25 277 600 0-60 20 4 4 10 20
DMC-FCP-22-30 30 277 600 0-60 20 4 4 10 20
DMC-FCP-22-4×30 4×30 16 60
DMC-FCP-22-50 50 277 600 0-60 24 4 4 6 25
DMC-FCP-22-75 75 277 600 0-60 24 4 4 6 25
DMC-FCP-22-100 100 277 600 0-60 29 4 ½ 4 ½ 2 30
DMC-FCP-22-150 150 277 600 0-60 31 8 5 ½ 4/0 60
DMC-FCP-22-200 200 277 600 0-60 31 8 5 ½ 4/0 60

DMC-FCP-22 Series 60 Hz in Dual, Triple* and Quadruple configuration DMC-FCP-23 Series available for 400 Hz

 

DMC Part No*

Current (AMPS) Line to Ground Voltage Frequency (Hz) Dimensions (Inches)  

AWG

APPR WT

(LBS)

VAC VDC A B C
DMC-FCP-22-2×30 2×30 277 600 0-60 20 8 4 10 40
DMC-FCP-22-2×50 2×50 277 600 0-60 24 8 4 6 50
DMC-FCP-22-2×63 2×63 277 600 0-60 24 8 4 5 50
DMC-FCP-22-2×100 2×100 277 600 0-60 29 9 4 ½ 2 50
DMC-FCP-22-4×30 4×30 277 600 0-60 24 16 4 6 100
DMC-FCP-22-4×63 4×63 277 600 0-60 24 16 4 6 100
DMC-FCP-22-4×200 4×200 277 600 0-60 31 23 12 2 400

Specifications

ELECTRICAL

CURRENT RATING: The filters shall be capable of withstanding 140% of rated current for 15 minutes without deterioration

INSERTION LOSS: The filters shall provide specified insertion loss of 100 db minimum over its indicated frequency range when measured in accordance with MIL-STD-220A,

VOLTAGE: The filters shall be capable of operating continuously at full- rated voltage and withstanding an initial test of twice the rated voltage for one minute ,

 

MECHANICAL

CASE: The filter case shall be made of cold-rolled steel

CONSTRUCTION: Input and output terminals shall be completely enclosed in RF shielded compartments. Cover on the input compartment shall be screw-down type

FINISH: All filter cases shall be made corrosion-resistant with suitable plating

IMPREGNANT: The impregnant shall be non-flammable as classified by UL and MIL-F-15733

TERMINALS: The terminals shall be made of high temperature ceramic